Description
75 hp (55 kW) heavy duty variable frequency drive for energy savings, three phase 230V, 440V, 480V for choice.
Specification:
| Basics | Model | GK3000-4T0550G/ GK3000-2T0550G |
| Capacity | 75 hp (55 kW) | |
| Shipping weight | 31 kg | |
| Dimension | 555*310*260 mm for GK3000-4T0550G/ 650*400*300 for GK3000-2T0550G | |
| I/O Feature | Rated current | 110A at 380V ~ 480V, 210A at 220V ~ 240V |
| Input voltage | 3 phase 230V /440V /480V AC ±15% (Optional) | |
| Input frequency | 50Hz/ 60Hz | |
| Output voltage | 3 phase AC 0~input voltage | |
| Output frequency | 0Hz~1000Hz | |
| Over load capacity | 150% of rated current for 1 minute, 180% of rated current for 3 seconds | |
| Control Feature | Control mode | V/F control; Sensorless vector control; |
| Communication | RS485 | |
| Speed regulation | 1:100 | |
| Start torque | 150% of rating torque at 1 Hz | |
| Speed control accuracy | ≤±0.5% of rating synchronous speed | |
| Frequency precision | Digital setting: max frequency x± 0.01%; Analog setting: max frequency x± 0.2% |
|
| Frequency resolution | Analog setting: 0.1% of max frequency; Digital setting: 0.01Hz |
|
| Torque boost | Automatic torque boost, manual torque boost 0.1%~30.0% | |
| Interior PID controller | Be convenient to make closed-loop system | |
| Automatic energy save running | Optimize V/F curve automatically based on the load to realize power save running | |
| Automatic voltage regulation (AVR) | Can keep constant output voltage when power source voltage varies. | |
| Automatic current limiting | Limit running current automatically to avoid frequent over-current which will cause trip | |
| Environment | Enclosure rating | IP 20 |
| Temperature | –10℃~ +40℃; VFD will be derated if ambient temperature exceed 40℃; each rise 1℃, the derate will be 5% | |
| Humidity | 5%-95%, without condensation | |
| Altitude | ≤1000m; VFD will be derated if above 1000m | |
| Impingement and oscillation | Normal running:<5.9m/s2 (0.6g); Transportation:<15m/s2 (1.5g) | |
| Store environment | –20℃~ +60℃; no dust, no corrosive gas, no direct sunlight |
Note: ATO VFD Cannot be used as a power source, it Can only be directly connected to an induction motor to control the motor speed.
Tips: Variable Frequency Drive Overload
Overload is also one of the frequent failures of VFD. When meet with the problem, we should first analyze if the motor overloads or VFD itself overloads. Generally speaking, the motor has high overload capacity, as long as the VFD parameter is set properly, it will not appear motor overload. But the VFD overload capacity is relatively not high. It is easy to appear overload alarm. We can detect the VFD output voltage, output current, and detect circuit and other trouble points one by one for trouble shooting.
For example, a 75hp VFD often displays “OL” when running.
Analysis and maintenance: According to the response from customer, this VFD was originally used in the 50hp motor, but now it is used for 75hp motor without resetting any parameters, so the problem may be out on the parameters. After checking, set VFD limit current as 75hp motor rated current instead of 50hp, and finally the problem is solved.