Description
The active and reactive combined transducer is an integrated measurement device that can monitor the active and reactive power in the power system at the same time and provide comprehensive power parameter data. The active and reactive combined transducer can reduce the installation space and wiring complexity, and reduce the cost of multi-sensor deployment. The active and reactive combined transducer is calculated based on the voltage and current signals at the same time to avoid errors caused by time differences.
Specification
| Model | ATO-PT-HDB-PQ3 |
| Measurement | 3phase 3wire or 3phase 4wire (optional) |
| Input | AC Voltage: 57.7V, 100V, 220V, 380V, 450V, 660V, customization AC Current: 1A, 5A, 10A, 20A, customization (optional) |
| Input Load | CT of voltage transformer: ≤0.1VA CT of current transformer: ≤0.2VA |
| Allow Overload | Voltage × 2 times the nominal value continuous Current × 2 times the nominal value continuous Current × 10 times the nominal value for 10s |
| Accuracy | 0.2, 0.5 (optional) |
| Response Time | ≤400ms |
| Output Channel | 1 channel, 2 channels, 3 channels, 4 channels (optional) |
| Output Voltage | 0-10V, 0-5V, 1-5V (load resistance = input voltage/10mAdc) |
| Output Current | 0-1mA, 0-10mA, 0-20mA, 4-20mA (Load resistance=10VDC/output current) |
| Other Output | RS485, customization |
| Output Ripple | ≤0.5% RO peak |
| Work Environment Temperature and humidity | 0~50℃/less than 80% relative humidity (non-condensing state) |
| Storage conditions temperature and Humidity | -20~70℃/less than 70% relative humidity (non-condensing state) |
| Aux.power Supply | DC12V, DC24V, AC220V, DC220V, AC110V, DC110V, 2-wire circuit power supply (optional) |
| Isolation | Input/output/power supply/shell |
| Power Consumption | DC about 3W, AC about 4VA |
| Material of Shell | ABS fireproof material |
| Weight | About 650 grams |
| Compressive Strength | AC2kVrms/min |
| Insulation Resistance | >100MΩ at DC500V |
| Dimensions | 120(L)× 110(W)× 75(H)mm |
| Installation Method | 35mm standard rail or fixed on the cabinet |
Dimension (Unit: mm)
Calibration Fine Tuning
PWR: Power indicator
SPAN: Calibration full scale potentiometer
ZERO: Zero potentiometer
Wiring
Tips: Advantages of active and reactive combined power transducer
- Save space and cost: Measure active and reactive power simultaneously with a single device, reducing the need to install multiple independent transducers, hardware costs and wiring complexity. Suitable for scenarios with limited space (such as distribution cabinets, and compact equipment).
- High data synchronization: Calculate active and reactive power based on voltage and current signals at the same time point, avoiding data asynchrony caused by the sampling time difference of split sensors.
- Easy maintenance: Only a single device needs to be calibrated, reducing the workload of calibrating split transducers one by one. The centralized design facilitates monitoring and diagnosis, reducing maintenance difficulty.