Megger Insulation Tester, 500V/1000V/2500V/5000V
Sale!

Megger Insulation Tester, 500V/1000V/2500V/5000V

Original price was: £1,132.30.Current price is: £226.46.

SKU: ATO-IRT-UT513A Category:

Description

Digital Megohmmeter or Megger insulation tester has selectable test voltages of 500V, 1kV, 2.5kV and 5kV with the capabilities of testing insulation resistance up to 1000 MΩ, ideal for testing high voltage equipment such as transformers, genera-tors, high voltage motors, power capacitors, power cables, arresters and so on. The megger is an ideal tool for electric maintenance, testing and inspection.

Specification

Model ATO-IRT-UT513A
Insulation Resistance (Ω) Test voltage/accuracy 500V/1000V/2500V/5000V 0% ~ 20%
Measurement range/accuracy 500V 1 MΩ ~ 20 GΩ ±(3%+5)
1000V 2 MΩ ~ 40 GΩ ±(5%+5)
2500V 5 MΩ ~ 100 GΩ ±(3%+5)
5000V 10 MΩ ~ 1000 GΩ ±(3%+5)
Short-circuit current >3.0mA
DC Voltage (V) Test range/accuracy 600V ±(2%+5)
AC Voltage (V) Test range/accuracy 600V ±(2%+5)
Features Display 9999 counts
Auto ranging Yes
Auto power off Yes
Low battery indication Yes
Data storage 18
Comparison measurement Yes
PI Yes
DAR Yes
USB port Yes
LCD backlight Yes
Analog bar graph 30
Over-range warning Yes
High voltage indication Yes
Timing measurement (Around 15 min) Yes
General Power supply 1.5V battery (LR14) x 8
Display size 123mm x 58mm
Operating temperature 0℃ ~ 40℃ (32℉ ~ 104℉)
Storage Temperature -20℃ ~ 60℃ (-4℉ ~ 140℉)
Relative Humidity ≤85%RH @ 0℃ ~ 40℃ below;
≤90%RH @ -20℃ ~ 60℃
Product weight 2kg
Product size 202mm x 155mm x 94mm
Standard accessories * 2*single plug test lead with alligator clip (black and green), 1*double plug test lead with alligator clip (red), batteries, USB cabel, PC software CD

Note: * Batteries are Not Included for air shippment.

Insulation Resistance Test Wiring Diagram

Details

Tips: What should you prepare before using an insulation resistance tester?

When Megger is working, it generates high voltage, and the measuring object is electrical equipment, so it must be used correctly, otherwise it will cause personal or equipment accidents. Before use, the following preparations should be made.

  • Before the insulation resistance measurement, the power supply of the equipment under test must be cut off, and the equipment is discharged by short-circuiting to the ground. It is never allowed that the equipment to be charged is taken for measurement. Nevertheless, the safety is in the first place.
  • For devices that may be induced by high voltage, the possibility must be eliminated before measurement can be made.
  • The surface of the measured equipment should be clean to reduce the contact resistance and ensure the accuracy of the measurement results.
  • Before the insulation resistance test, check whether the Megohmmeter is in normal working state, that is, mainly checking its “0” and “infinity” points. That is, shake the handle to make the motor reach the rated speed, the meter should be in the “0” position in the short circuit, and in the “infinity” position in the open circuit.
  • The insulation resistance tester should be placed in a stable, firm place, and away from the large external current conductor and external magnetic field.

After the above preparations are made, the resistance measurement can be carried out. During the testing, the correct wiring of the Megger insulation tester should be paid attention to, otherwise unnecessary errors or even errors will be caused.